BS/BT | Indoor Split

GeoComfort BS/BT indoor split heat pumps provide ducted heating and cooling and domestic hot water. These systems can be paired with a conventional furnace to create a dual-fuel system. The BS/BT heat pumps can be used for heating and cooling in residential developments, schools, public institutions, office buildings, etc.

COMPATIBLE WITH THE EPIC CONNECTED CONTROLS

Our proprietary EPIC connected controls provide unprecedented insights into the usage, efficiency, and performance of your geothermal system – all in real time! See how to maximize your home’s comfort with EPIC.

COMPATIBLE WITH THE DX AIR HANDLER - BUILT BY ENERTECH

Unlock the full potential of your geothermal split system for forced air applications with the direct expansion (DX) air handler.

FEATURES

  • Available sizes: 1.5 to 6 tons
  • Efficiencies: Up to 28.8 EER / 4.4 COP
  • Hot water assist
  • UL GREENGUARD Gold certified cabinet insulation
  • Heavy gauge steel
  • Two-stage compressor
  • Temperature sensor as part of system safeties
Document Downloads:
Model Specifications:
Model BS018
CAPACITY Full Load Part Load
COOLING BTU/HR 21,800 -
COOLING EER 21.10 -
HEATING BTU/HR 18,800 -
HEATING COP 3.90 -
Model BT024
CAPACITY Full Load Part Load
COOLING BTU/HR 26,300 21,500
COOLING EER 19.50 27.80
HEATING BTU/HR 18,800 15,400
HEATING COP 3.90 4.30
Model BT036
CAPACITY Full Load Part Load
COOLING BTU/HR 36,900 29,300
COOLING EER 19.20 28.90
HEATING BTU/HR 27,800 22,600
HEATING COP 3.80 4.30
Model BT048
CAPACITY Full Load Part Load
COOLING BTU/HR 50,300 39,600
COOLING EER 18.40 27.10
HEATING BTU/HR 40,700 32,100
HEATING COP 3.80 4.40
Model BT060
CAPACITY Full Load Part Load
COOLING BTU/HR 61,100 48,100
COOLING EER 17.60 24.30
HEATING BTU/HR 46,800 38,200
HEATING COP 3.80 4.20
Model BT072
CAPACITY Full Load Part Load
COOLING BTU/HR 67,200 54,900
COOLING EER 15.80 21.10
HEATING BTU/HR 57,300 47,700
HEATING COP 3.40 3.80
GeoComfort
by Enertech Global, LLC
2506 S Elm Street
Greenville, IL 62246